Thursday, September 25, 2008

POWER SYSTEM RELIABILITY IN INDUSTRIES - PART III

RELIABILITY OF INDUSTRIAL PLANT POWER SYSTEM – PART III
by Doods A. Amora, PEE

VOLTAGE DIPS & SAGS




VOLTAGE DIPS & SAGS IN INDUSTRIAL PLANTS


Voltage Dips & Sags and their impact on plant operation constitute the most frequent and most noticeable reliability problem in the distribution systems of industrial plants. Spoiling Reliability, voltage dips can result in trip-outs of plant equipment - shutting down manufacturing lines leading to production loss and expensive re-start procedures.

These system disturbances can be grouped into three general types:

Voltage Sag is a partial reduction in the magnitude of voltage that often persists for extended periods and is usually related to system loading conditions.

Voltage Dip is a significant reduction in voltage for a relatively short duration, often caused by power system faults, or as frequently in events of large motor starts-up.

Voltage Interruption is a complete loss of input voltage, lasting from seconds to a much longer time.

Inside the industrial plant, voltage dips may be caused by faults somewhere in the other parts of the distribution system and more frequently by large motor starts-up in already loaded transformers. Common in heavy industrial plants, voltage sags are caused by heavily loaded transformers with poor voltage regulation and relatively lengthy distribution lines.


Utility system Voltage Dips are often caused by bad weather conditions (thunderstorm, etc), or utility equipment failures, or faults in some other areas of the utility system; and can last anywhere from a few cycles to seconds or more. Voltage Sags in utility systems on the other hand, are related to voltage drops along transmission lines and more prevalently by system loading conditions, as well.

Voltage Interruption is the complete loss of voltage and usually require a source of energy to replace the utility supply.

There are several mechanisms by which voltage sag or dip can interfere with industrial manufacturing processes, as follows:


Control Error – Loss of control power results in the inability to control the process.

Contactor Dropout – Many industrial controls employ magnetically-latched contactors as motor control devices. A voltage dip or sag can cause a momentary collapse of the magnetic field which holds the contacts closed. When the contacts open, the motor stops.

Voltage Flicker – In the practical sense, flicker is the repetitive variation in intensity of lighting, and is more of a human irritation factor (threshold of perception, or threshold of human objection) than a direct cause of process disruption. However, it can also be used in a more literal sense to describe a set of problems in which lighting is extinguished due to voltage dips.

Machine Dynamics – Since voltage magnitude is essential to transmitting power, voltage dips and sags limit the ability of a power system to distribute power from sources to loads. This limitation in power transfer can lead to generators not being able to maintain stability.

Stall & Re-Acceleration – Motors will stall if the supply voltage is depressed for a prolonged period. Furthermore, motors must reaccelerate when normal voltage is restored. Reacceleration involves higher than normal motor currents which may result in further voltage sag problems.


MITIGATING VOLTAGE SAGS

As system modifications can be implemented to minimize the magnitude and duration of voltage dips & sags; these modifications too, don’t come in cheap. However, if the vulnerability of the system is understood, the system engineer may well identify the only selected critical areas that require modification. Or if several problems can be solved with “one stone hitting several birds”, then these capital outlays would come up in reasonable proportions.


So then, voltage dips & sags generally imply solutions that provide some means of supporting voltage. One good voltage support scheme is the ‘On-Load-Tap-Changer’ (OLTC) usually in large substation power transformers. Other schemes could be the Automatic Voltage Regulators (AVR’s) which are separate apparatuses from the transformer but somehow perform similar function as the OLTC’s. While the OLTC’s are accomplished in the primary winding side of the transformer, the AVR’s are preferred voltage correction at the secondary output side. Smaller voltage support apparatuses could be the Voltage Stabilizers which are for control systems. Again, these don’t come in cheap.

Because of the diversity in sub-distribution system peaks, OLTC’s are very effective in primary substations which are usually upstream of several layers of smaller downstream substations. But at the intermediate voltages of 3.6 kV, 4.16 kV or 6.9 kV where large motors are populating, the performances of OLTC’s and AVR’s may be found wanting because of their inherent time delay responses. Note that the time delay is designed purposively in these equipments. OLTC’s and AVR’s don’t just react instantaneously, as the logic of these apparatuses would first make sure that the voltage variation is real and not just fleeting spikes. This is to prevent hunting or wild operation. They too, have contacts immersed in oil. The contacts wear rapidly and the oil need frequent replacements. And operation must be interrupted more frequently.


VULNERABILITY TO VOLTAGE DIPS

There are many things that could happen during voltage dips. Generally, for a running motor for instance; as the supply voltage to the motor decreases considerably during voltage dips, the motor speed decreases. Depending on the depth and duration of the voltage dip, motor speed may recover to its normal value as the voltage amplitude recovers. If the voltage dip magnitude and/or duration exceed certain limits, the motor may stall and would be taken out of the system by the means provided for in its controls. Maximum voltage dip magnitude and/or duration, which the motor operation can survive, depend on the motor parameters and the torque-speed characteristic of the driven load.

On the other hand, when a large motor is started-up in an already sagged voltage of an already loaded transformer source, the ensuing resultant voltage dip during motor starting may cause the motor to stall and could not complete the starting process. As discussed above, this scenario would also affect the running motors, as they too may stall - aggravating the problem in a domino effect. In this scenario, currents fly high and something somewhere has to trip to relieve the system from further disturbance.


SYSTEM BEHAVIOR DURING LARGE MOTOR START-UP


Transformer reactions to large motor-starting are manifested in voltage dips. In general terms, transformers in an electrical system are usually larger than the maximum demands they serve, in some instances even larger than the connected loads. In the industrial plant scenario, the obvious reason at first glance for this apparent oversizing is the anticipation for future load growth. Fine…

But more often than not, sizing the transformer with extra kVA capacity unwittingly addresses voltage dip problems, not for load growth for which it is intended originally. That’s why for newly constructed plants where load growth is not yet there, the problem of starting significantly large motors may not surface out. Why? Because the extra kVA capacity intended for load growth is taking care of it.

Now, when the plant is already 25 years old and a series of expansions & load growths had been in place, the transformers may now be loaded near their full load ratings. Fine…the transformer can still handle it. However, effects of voltage regulation (which is normal to transformers) this time would surface out. The voltage difference between loaded and unloaded output of a transformer is voltage regulation. Voltage Regulation in transformers is normal – meaning, as the load increases there is a decrease in voltage output due to the corresponding voltage drop within the primary and secondary windings.

Now if a 3.6 kV transformer (transformer terminal voltage of 3.6 kV by North American Norms) has a voltage regulation of 8% (which is usual); the voltage at the secondary terminals in a fully loaded transformer would then be 3.3 kV. If the same transformer is 80% loaded, the voltage at the secondary terminals of the transformer may have been in the vicinity of 3.37 kV. What happens then when a 2,300 kW or a 6,400 kW motor is started up? There would surely be voltage dip! By how much..? And how much voltage dip can cause problems?


BEHAVIOR OF LARGE MOTOR START-UP

Partly similar to short circuit condition, motors have a high initial inrush current when energized at a low power factor (0.30 lagging for 100 hp & about 0.16 for 1,000 hp motor) from standstill. This sudden increase in the current flowing to the load causes a momentary increase in the voltage dip at the supply transformer terminals, the drop along the distribution system, and a corresponding reduction in the voltage at the utilization equipment.

The magnitude of transient current involved in motor starting is however lower than the short circuit condition. But in effect, switching “on” to energize a large motor can be likened to a “soft short circuit”. Like short circuits, the effect of starting large motors results to huge voltage dips but lower in magnitude than the full short circuit scenario.

The voltage drop at the transformer secondary terminals is proportional to motor starting kVA over the short-circuit capacity of the transformer. When motor starting kVA is drawn from a system, the voltage drop in percent of the initial voltage is approximately equal to the Motor Starting kVA divided by the Sum of this kVA and the Short Circuit kVA (Motor Application & Maintenance Handbook by Robert W. Smeaton, 1969 Edition).


SUBSTATION TRANSFORMERS Vs. LOADS

Because of the effects of Transformer Voltage Regulation and Voltage Dips in starting large motors, North American motors after mid 1960’s are rated at 230, 460, 2,300, 4,000, 6,600 or 13,200 volts for use with distribution systems that are rated at 240, 480, 2400, 4,160, 6,900 or 13,800 volts respectively. Again, note the difference in motor nameplate voltages viz-a-viz the transformer terminal voltages. The apparent higher distribution nominal voltages than motor voltages are deliberately established by transformer and motor manufacturers to deal with the inherent voltage drops in the system such as: internal voltage drop of the transformer as dictated by its voltage regulation capability, voltage drop along the distribution cables and the impedance of the system. This could mean that a transformer could be 4,160v at no-load condition may only be 4,000v or less at the motor terminals when the system is already heavily loaded. While in this condition, when a large motor is started-up somewhere in the system, the more critical will the voltage be as felt by other loads in the system.

The “nominal system voltage” is the terminal voltage of the transformer. Per General Electric (Prolec) Publication, “secondary voltage ratings are approximately 4.2 percent above the standard motor voltages, allowing for voltage drop in the line between the substation and the motor terminals without operating the motor at subnormal voltage. Motors and control operate satisfactorily on voltages 10 percent above or below rating.”

In some IEEE proceedings, a question has been raised why the utilization equipment voltage ratings and system nominal voltage cannot be made the same. Manufacturers’ response is that the performance guarantee for utilization equipment is based on the nameplate rating and not on the system nominal voltage.

SIDEBAR: THE LOWEST ACROSS-THE-LINE STARTING VOLTAGE THAT MOTOR MANUFACTURERS GUARANTEE IS 90% OF THE MOTOR NAMEPLATE VOLTAGE,- NOT ON THE NOMINAL VOLTAGE .RATING.

That’s why most motors are designed to be capable of operating at plus or minus 10% of nameplate voltage. Therefore, the voltage drop on inrush should not be allowed to drop more than 10% of the rated voltage. This means 208v for 230v or 414v for 460 volt motors. Likewise, 2.07 kV for 2.3 kV motors, or 3.6 kV for 4.0 kV motors. It means that a 4.0 kV motor can still operate satisfactorily at 3,600v but any disturbance in the system that brings the system voltage lower, the affected motors may trip off as provided for by its protection – or if not, the motor burns.

Hence, the wisdom of employing “reduced voltage stating methods” are common to large motors in order to reduce the voltage dips during starts-up. Foremost of these mitigating starting methods are: reduced voltage auto-transformer type, soft starters, and variable frequency controllers for squirrel cage induction motors and resistor starting (liquid or hard resistor) types for wound rotor induction motors.


ECONOMIC EVALUATION

While the stability of the incoming supply voltage is fundamentally a technical problem, at the end of the day, it is business sense that makes decisions in implementing a fix. Some solutions to voltage dip and sag problems require the use of exotic technology. Today, terms like: “voltage dip-proofing” or “voltage dip & sag immunization” are already a reality, but then again, they don’t come in cheap – and may be prohibitive!

A major influencing factor concerning the financial loss is whether or not the factory production is continuous. As practiced by many industries, continuous production means that there is market to all products that a company can produce. In continuous production, the production lost during downtime cannot be recovered by working extra time, so loss of production translates directly into loss of profit – that is, the loss is equal to the value of the product not produced as a result of the downtime.

In a non-continuous process, lost production can be recovered by overtime working, although there may well be additional labor & utilities consumption costs.

Whether or not a solution is seen as cost-effective thus depends on the economic criterion that is used to evaluate the solution. The actual economic justification in preventing production interruptions due to voltage disturbances must therefore consider the following elements:


1) How vulnerable is the process to various types of voltage disturbances?

2) What is the net cost of production outages due to these disturbances?

3) How effective is a particular solution in avoiding these outages?

4) How does the cost of the solution compare to the savings which can be realized?


As to the cost associated with voltage interruptions the following elements should be recognized and quantified:

Cost of Lost Production – In the simplest case, this is the incremental margin on products that cannot be sold because they are not manufactured.

Cost of Damaged Product – If the interruption damages a partially completed product, the cost of repairing that product must be recognized. In some cases, the product cannot be repaired, so the value of the raw materials (including the consumed energy and other manufacturing costs up to the point where the disruption occurred) must be accounted for together with the cost of the incremental value added to the product.

In other environments, a major source of concern is lost computer data.

Cost of Maintenance – This is the cost of reacting to a voltage disruption. This includes everything involved in restoring production, including trouble-shooting and correcting the problem, cleanup and repair, disposing of damaged product, and environmental costs.

In some industries (e.g., plastics, glass manufacturing, cement manufacturing, electronics, etc), an interruption may result in the need to invest many days and a significant amount of money in cleaning up the process system before it can be returned to service.

Hidden Costs – This factor may be the most difficult to quantify but it can easily be the most significant. If the impact of the voltage dip or sag is control error, it is possible that the impact on product may not be apparent until the product is in the hands of the consumer. As business nightmare, product recall and the subsequent public relations costs can be significant or may even cause bankruptcies.

It is usually best to identify the problems that are responsible for Plant Reliability, and apply solutions that most efficiently address those gaps.

If the manufacturing plant does not design its system with reliabilty and quality in mind, SOMEONE ELSE WILL.

DAA
Sept, 2008

Thursday, September 11, 2008

POWER SYSTEM RELIABILITY IN INDUSTRIES - PART II


RELIABILITY OF INDUSTRIAL PLANT POWER SYSTEM -
PART II

by Doods A. Amora, PEE




THE PILLARS OF RELIABILITY

Are “RELIABILITY NINES” achievable…?

Reliability could partially mean the best equipment or systems that are the easiest to repair or maintain. That’s maintainability.

But on top of these, redundancy is still needed. Highly reliable systems often include multiple power supplies, UPS’s (stationary or rotary), backup diesel generators (for longer power outages) and extras of whatever else is likely to fail. Troublesome equipment & apparatuses that break down a lot and take a long time to get back online are going to spoil reliability. So, the chosen system depends on the duration of outage the plant can tolerate. Diesel generator sets require about 5–10 seconds to start, come up to rated speed, develop rated voltage, and begin to powering up loads. Where even momentary outages are unacceptable, UPS or flywheels (rotary UPS’s) are now common.

Note that the concept of ‘Reliability Nines’ can be achieved through:


1) Good Design of the System
2) Effective Maintenance Program
3) Error-Free Operation

While it is true that reliability is fundamentally influenced by the sturdiness of equipment & apparatuses in the system, trouble-free operation and effective maintenance starts at the drawing board when the design of a system is conceptualized. The design of an electrical system is to provide continuous operation under all foreseeable circumstances, including utility outages and equipment breakdown. When considering the implications of reliability, all three pillars of system reliability: design, operations, and maintenance, must be inputted in the design concept.

Experts in Reliability say, “There is no maintenance program that can improve the reliability of a poorly designed system. Additionally, whatever maintenance program developed by a plant is determined by the design of the system and the goals of the organization. One goal for reasonable levels of reliability given the nature of the technology is a good selection of equipment or system that provides a Mean Time Between Failure (MTBF) that is as long as possible. It is desirable to have a few relatively long but planned service interruptions rather than lots and lots of short ones that are unexpected. Maintenance also aims to provide a Mean Time To Resolution (MTTR) that is as short as possible, so that when a failure does occur service can get back quickly”. Again, this is maintainability.


Reliability practitioners further say, “The telephone system is a good example of reliability improvement over time. When telephones first became widely available in the early twentieth century, their reliability was poor by today's standards, with outages, dropped calls, line noise and crosstalk quite common. As time passed, technology improved to the point where five nines of reliability are now common. It did, however, take nearly eighty years to reach that standard of reliability”.

For sure, reliability comes at a cost - and it doesn’t come in cheap. For electric systems of any manufacturing plant for that matter; operational continuity frequently is synonymous to 'how fast the restoration of electric service' is. But swift restoration of service can not be achieved when there are no alternate paths of power flow provided in the system.


REDUNDANCY IN THE ‘N + n’ SYSTEMS

Hereunder is to introduce the terms, [N + 1], [N + 2], [N + 3]… as reliability through good system design:

1) A system with one redundant path is termed an N+1 design.

2) N + 1 would allow for one of the paths to be de-energized for maintenance while the other is still energized, allowing maintenance without system shutdown.

3) If the system is designed with a normal path and two alternate paths (N+2 design), one path could be down for maintenance, a failure could occur in a second path, and ideally, the third path would supply power to the load without interruption.

Thus new reliability jargon has given rise to the novel terms as: N+1, N+2, N+3 or N+n which speak for the degree of redundancy. How then does the Power System of an industrial plant fare with the ‘N + n’ principle?

Note that in a system that has been operating for 20 years, the more honest-to-goodness maintenance is needed to sustain continuous operation. But decent maintenance (other than wiping, air-blowing or cleaning the externals of the equipment & apparatuses) can not be done if there is no degree of redundancy in the system. Chances are, maintenance time would only be a few hours usually allocated during scheduled plant-wide annual shutdown. In this case, maintenance becomes superficial and hasty as production group would be scratching their backs when schedule to re-start operation has come.

So then, maintenance can’t be effective if the plant itself is not designed to be ‘maintainable’. The power system configuration must be maintenance-friendly such that maintaining major equipment does not mean shutting down the plant. If maintenance requires shutting down the plant, so then the plant is "not maintainable”. If continuous round-the-clock operation of all or some identifiable parts of the process is required, then system configuration must have redundant feeders or separate supplies to these components to support maintenance at other portions of the system. The power system must also be flexible in events of failures of major equipment such that the plant can still operate partially in a considerable production capacity.

But then, redundant power supplies in some instances do not always improve reliability. If two redundant feeders supply power to an industrial facility but originate at the same utility substation and are carried on the same set of power poles, reliability will be lower than if they originate at separate substations and travel to the site on different sets of power poles. The problem with redundant feeders carried on the same set of poles is that a single-point failure (e.g., a weather-related event, pole fire, or traffic accident) could cause simultaneous outages on both sources.

RATIONALE OF THE RELIABILITY STUDY

The importance of a Reliability Audit can not be over-emphasized. Its value speaks for itself the moment power is out during peak production days or during the visit of the company president. An industrial plant therefore continues to face the challenge of improving its power system availability of existing facilities in a very competitive global market. These challenges are aggravated by the condition that many plant facilities may have been in operation for more than 20 years with constant exposure to corrosive materials, fumes and a hostile environment which contribute to the gradual deterioration of equipment integrity. As the plant grows older, poor system availability may mean loss of competitiveness.

Experience has shown that capital investments to extend the life of facilities can be expensive if these are done when reacting to unplanned outages. Industry’s best practices are aimed to maximize reliability, and minimize unplanned production losses by using structured systems that implement pro-active reliability programs.

Note that if the industrial plant is already 20 years old, a sort of a Reliability Assessment should be sought for. Of course, reliability assessment should have been wanting during the drawing board conceptualization but an assessment today would not place the effort for naught. After 20 years, this kind of assessment is even more meaningful as a lurking system fault increases with age. This study therefore is used to identify improvement opportunities and manage to sustain system reliability in a cost effective manner.

The Reliability Assessment for an industrial plant may have the following objectives:


1) To identify “system vulnerabilities” or “gaps” that includes the following:

a) Loading Behavior or Load Profile of the Primary & Intermediate Substations that could have resulted to over-stresses and poor voltage regulations,

b) Review on the Flexibility of the System with regards to power supply and feeders, its capacity or capability in supporting the loads in alternate paths,

2) To identify major deviations from normal industry practices, including but not limited to:

a) Voltage-Dip levels on each major feeder or intermediate substations during starting of large motors and under other operating conditions,

b) Review on the Power Factor condition of each substation or feeder,


3) To identify whether the power system is resistant to faults & failures to include but not limited to the ability of a device or system to perform a required function under fault conditions and the ability of the system to "fail well". This includes the following:

a) Review & Confirmation of Actual Fault Duties against Interrupting or Momentary Ratings of the Existing Sets-Up,

b) Engineering Calculations Leading to Coordination and/or Discrimination of Protective Devices within the entire system,

c) Actual Re-setting, Testing & Simulations on these Protective relays whether they are performing as expected,

d) Evaluate actual condition of the equipment & apparatuses within the system if they could still last longer than expected.

4) Recommend measures to close identified gaps & vulnerabilities, including application of technology and/or system modifications that will facilitate improvement in reliability, as follows:

a) Capacity Review on all electrical equipment whether additional capacities are necessary to maintain reliable service under various operating conditions.



To be continued...

DOODS (September, 2008)

Sunday, September 07, 2008

POWER SYSTEM RELIABILITY IN INDUSTRIES


RELIABILITY OF INDUSTRIAL PLANT POWER SYSTEM -
PART I

by Doods A. Amora, PEE



WHAT IS RELIABILITY?


This article is an assimilation of the interwoven factors & issues that contribute to the reliability of power systems in industrial plants. As Reliability is a broad scope, understanding what it is, comes first.


IEEE defines RELIABILITY as "the ability of a system or component to perform its required functions under stated conditions for a specified period of time." Likewise, from the Wikipedia, Reliability may be defined in several ways, as follows:


* The idea that something is fit for a purpose with respect to time;

* The capacity of a device or system to perform as designed;

* The resistance to faults or failures of a device or system;

* The ability of a device or system to perform a required function under stated conditions for a specified period of
time;

* The probability that a
functional unit will perform its required function for a specified interval under stated conditions.

* The ability of something to "
fail well" (to fail without catastrophic consequences and is restorable in a reasonable period of time).


RELIABILITY IN EVERYDAY LIFE

In the Philippines, electricity is usually taken for granted. As many observers say, ‘electrical power is somewhat like the air people breathe’. Electricity seems to be just ‘in there,’ meeting every man’s need constantly, somewhat eternally. As it is always expected that light would come on every time a switch is flipped, fact is, humanity doesn’t really think about it until it is lost. It is only during a power failure, when one enters into a dark room and instinctively hits the useless switch, realizing how important power is in daily life. But, a reliable & continuous presence of electricity is more than just comfort or convenience. It's a necessity. Take power out and industries will grind to a halt - the nation’s economy, as well. Without it today, life gets clumsy and gawky.

In an industrial plant scenario for instance: It’s only a matter of pushing a button and a 6,000 kW motor kicks up to life - just like that! And nobody seems to be thinking about it. That in a sense is reliability..! But if somebody is worrying about what could result if a button is activated (e.g., huge voltage dips or source trip-outs), then that’s another story…

Now, if nobody seems to be worrying about it - then that is good reliability..! Thus, in practical terms, power system reliability is simply: “There is power at sufficient capacity when needed, at any given time, all the time..!”

For an industrial plant, maintaining a high level of reliability requires continuing purposive watch. Of course, a plant relies on a dependable interconnected network of generation (by NPC or PNOC or IPP’s), transmission (TRANSCO & other Power Distributors), and the industry’s own Distribution Systems to power up various processes of an industrial plant whose appetite for power may be small or big time. The questions thus, are:

1) What is the industrial plant’s desired condition in so far as operational continuity is concerned?

2) How long can the industrial plant endure a forced shutdown?


The type of process and the behavior of manufacturing operations of the plant dictate the continuity of service requirements of the power system. Some plants can tolerate interruptions while others require the highest degree of continuity. Where adequacy & continuity of service is of prime importance, these plants deserve a much higher degree of sophistication in their own distribution systems than others.


THE RELIABILITY ‘NINES’

So the question is – “What levels of reliability can a manufacturing plant live with?” First of all, we need to be oriented with the ‘Reliability Nines’ as a technical lingo.

The telephone network has always been identified as a good example of a highly reliable system. But then, bad weather conditions among other factors threaten to derail its high reliability for obvious reasons. As experts say, if the telephone system was out of service for a total of nine (9) hours over an entire year, then it was available for 525,060 minutes out of a possible 525,600 minutes. Its reliability is therefore: 525,060 divided by 525,600 minutes = .999”. Global experts label it as “three-nines” – and is a good reliability by most standards.

Note that the ‘Reliability Nines’ are new measurements for service dependability, consistency and trust-worthiness packaged in official terms as reliability. Depending on the nature of the business, the desired ‘nines’ in reliability depends on how essential the service is and what are the downtime benchmarks with other industries of similar nature. For telephone systems for instance, a nine-hour downtime per year may be excellent, but not acceptable for life-support systems in hospitals.

To compare with other types of services, the following new global standards may give some insights & discoveries as follows:

1) Homes: Three 9’s (99.9%), 9 hours downtime per year

2) Factories/Manufacturing Plants: Four 9’s (99.99%), 59 min/year

3) Hospitals, Airports: Five 9’s (99.999%), 5 minutes per year

4) Banks: Six 9’s (99.9999), 32 seconds per year

5) E-Commerce/ On-Line Markets: Nine 9’s, 30 milliseconds per year

As can be seen, reliability performance has got to do with the quality of services. In its everyday sense, quality of service means "consistency" and "repeatability". Reliability is when the service, whatever it is, is available or unavailable depending on one's perspective. A perfectly reliable system therefore is said to have a reliability of 1.0000, or a hundred percent reliable.


RELIABILITY IN THE MANUFACTURING PLANT

Note that with today’s technology, the ‘three-nines’ for telephone systems is no longer what the industry is looking at. The standard now often mentioned for traditional telephone service is the stiffer “five-nines”. This had become a motivational goal for new competing players, and a bragging right for those who have achieved it.

What about the factory? A factory or manufacturing plant supposedly belongs to ‘four-nines’. The expressed term ‘four-nines’ refer to the figure 99.99%. It's not just how frequent pieces of equipment in a power system burst into flames that solely counts. It's how much of the time the manufacturing plant is available for production. Availability already imbeds how often it breaks down and how fast it gets back into service. In addition, how long a system is out of service due to routine maintenance.


If a reliability of ‘two nines’ is acceptable to a manufacturing plant, this means that it could afford an average 87.6 hours of downtime annually (3 days, 15 hours and 40 minutes). To increase this reliability to four-nines, it means redundant systems where maintenance can be performed without necessarily shutting down production, while not loading the transformers, switchgears or cables heavily to their thresholds, and to make the system resistant to faults & failures and if it should fail, it should “fail well”.

“Failing Well” is what experts refer to in systems that sturdy enough to resist faults. And faults here mean that there shall be no disturbance to other systems that are unfaulted. The system therefore should be designed to isolate faults selectively with least disturbance to other parts of the system and should have the features for maximum reliability consistent with plant requirements. “Failing Well” also means that no damage in catastrophic proportions must result out of these faults. In Europe it is referred to as “fault control”.


To be continued…

DOODS (September, 2008)